Aerocel-SSPT® Pre-Split EPDM Insulation features a split-seal and over-lap seal with peel-off adhesives for a quick and simple installation. It meets 25/50 Fire and Smoke rating and has a working temperature range from -70°F to 257°F (-57°C to 125°C). For use in refrigeration and HVAC applications.
Low-density EPDM closed cell elastomeric foam, CFC and HCFC gas free.
Included Cell-Link II has no VOC emission.
0.235 (BTU * in/h *ft2 * °F) at 75°F.
<0.03 perm-in. (4.38 x 10-11g/Pa*s*m)per ASTM E96.
<0.2% by volume per ASTM C 209.
-70 °F to 257 °F (-57 °C to 125 °C) continuous per ASTM C 411.
Meets 25/50 Flame Spread/Smoke-Generated per UL 723 and ASTM E84. Additionally meets UL-94 5 V-A, V-0 and is self-extinguishing per ASTM D 635.*
NOTE: Has not been rated as a dual-layer assembly.
EPDM provides UV Resistance in accordance with ASTM G7/G90.
Meets ASTM D 1171.
Available in 6’ sections
Black
1/2", 3/4", 1", 1-1/2", and 2" available.